HRV / ERV INSTALLATION AND
OPERATING INSTRUCTIONS
Toll Free: 1.800.810.3473 (Canada)
1.866.890.6457 (U.S.A.)
790 Rowntree Dairy Road,
Woodbridge, ON Canada L4L 5V3
t: 905.851.6701
f: 905-851.8376
e: info@reversomatic.com
www.reversomatic.com
Maxum Series
model:
RHRV-S200A
Aluminum Core
RHRV-S200P
Polypropylene Core
RERV-S200
Enthalpy Core
Economy Series
model:
RHRV-E100A
Aluminum Core
RHRV-E100P
Polypropylene Core
RERV-E100
Enthalpy Core
Superior Series
model:
RHRV-S100A
Aluminum Core
RHRV-S100P
Polypropylene Core
RERV-S100
Enthalpy Core
C US
®
®
2100
CERTIFIED
Project Series
model:
RHRV-P100A
Aluminum Core
RHRV-P100P
Polypropylene Core
RERV-P100
Enthalpy Core

Questions and Answers

  • M
    Mark ClementsAug 14, 2025
    How to improve low airflow in my Reversomatic Furnace?
    • N
      Nicole FoxAug 14, 2025
      Low airflow in your Reversomatic Furnace can stem from several causes. Here's what to check: * **Improperly balanced HRV/ERV airflow:** Have a professional balancer or contractor balance the unit. * **Clogged filter:** Remove and clean the filter. * **Obstructed core:** Remove and clean the core. * **Blocked exterior fresh air supply:** Remove the blockage. * **Closed damper:** Check the damper. * **Restricting ductwork:** Inspect the duct installation. * **Low power supply:** Switch off the unit immediately and call the electrician to check the voltage.
  • B
    bradleykimAug 17, 2025
    What to do if my Reversomatic Furnace is not defrosting properly?
    • N
      Nicholas TorresAug 17, 2025
      If your Reversomatic Furnace isn't defrosting correctly, consider these potential causes: * **Frozen fresh air duct:** Check for and remove any ice. * **Improperly balanced HRV/ERV airflow:** Have a professional balancer or contractor balance the unit. * **Defective temperature sensor:** Replace the temperature sensor.
  • C
    christinewangAug 21, 2025
    Why is my Reversomatic RERV-S200 sensing cold air from the supply?
    • K
      Katrina MartinAug 21, 2025
      If your Reversomatic Furnace is sensing cold air from the supply, here are a few things to investigate: * **Blocked exhaust hood:** Remove any blockages and clean the hood outside the building. * **Improperly balanced HRV/ERV airflow:** Have a contractor balance the unit. * **Extremely cold outdoor temperature:** Consider installing a duct heater.
  • M
    Michael MeltonAug 25, 2025
    What does it mean when the LEDs on my Reversomatic Furnace flash twice?
    • K
      Kelsey PetersAug 25, 2025
      If the LEDs on the Main Control board and the remote wall mount Timer Switch of your Reversomatic Furnace are flashing 0.5 sec On/0.5 sec Off/0.5 sec On then 2 sec Off, then repeat the cycle (2 Blinks), it could indicate: * **Obstructed damper:** Check the backdraft damper to ensure no screw interferes with its function. * **Exhaust fan jam/over-current:** Replace the fan.
  • J
    Jeremy MatthewsAug 27, 2025
    Why doesn't the timer light stay on for my Reversomatic RERV-S200?
    • C
      Cynthia PetersenAug 27, 2025
      If the 20/40/60 minute light on your Reversomatic Furnace timer switch doesn't stay on, it might be due to: * **Loose connection:** Check the connection. * **Defective switch:** Replace the timer switch. * **Issue with main controller:** Reset the main controller.
  • G
    Gary WilsonAug 31, 2025
    What does it mean when the LEDs on my Reversomatic RERV-S200 Furnace flash three times?
    • H
      hughesjamesAug 31, 2025
      If the LEDs on the Main Control board and the remote wall mount Timer Switch of your Reversomatic Furnace are flashing 0.5 sec On/0.5 sec Off/0.5 sec On/0.5 sec Off/ 0.5 sec On, then 2 seconds Off, then repeat the cycle (3 Blinks), it indicates that the supply fan has an open circuit. This can be due to a burned motor or an overheated fan. Replace the motor.
  • J
    Joseph MendozaSep 3, 2025
    What does it mean when the LEDs on my Reversomatic Furnace flash four times?
    • S
      Shawn WeaverSep 3, 2025
      If the LEDs on the Main Control board and the remote wall mount Timer Switch of your Reversomatic Furnace are flashing 0.5 sec On/0.5 sec Off/0.5 sec On/0.5 sec Off/ 0.5 sec On/0.5 sec Off/0.5 sec On then 2 seconds Off, then repeat the cycle (4 Blinks), it could mean: * **Obstructed damper:** Check the back-draft damper, ensuring no screw interferes with its function. * **Supply fan jam/over-current:** Replace the fan.
  • D
    Daniel RowlandSep 7, 2025
    What does it mean when the LEDs on my Reversomatic RERV-S200 Furnace flash once?
    • K
      Kathleen DickersonSep 7, 2025
      If the LEDs on the Main Control board and the remote wall mount Timer Switch of your Reversomatic Furnace are flashing 0.5 second On then 2 seconds Off then repeat the cycle (1 Blink), it indicates an open circuit in the exhaust fan. This could be due to a burned motor or an overheated fan. Replace the motor.
  • L
    lewisstevenSep 9, 2025
    What does it mean when the LEDs on my Reversomatic Furnace flash five times?
    • K
      Kathryn PatelSep 9, 2025
      If the LEDs on the Main Control board and the remote wall mount Timer Switch of your Reversomatic Furnace flash 0.5 sec On/0.5 sec Off/ 0.5 sec On/0.5 sec Off/ 0.5 sec On/0.5 sec Off/ 0.5 sec On/0.5 sec Off/ 0.5 sec On/0.5 sec Off/ 0.5 sec On, then 2 seconds Off, then repeat the cycle (5 Blinks), it indicates a temperature sensor failure. In this case, both motors will shut off. Replace the temperature sensor.

Summary

Important Safety Instructions

Packaging Inspection

Check all parts and accessories for presence and good condition upon opening the box.

Parts List

Wiring Diagram

HRV and ERV Typical Installations

Typical Installations for House

Illustrates standalone HRV/ERV systems and semi-ducted systems for homes.

Installation Options for High-Rise Condominium

Shows installation configurations for high-rise buildings with fan-coil systems.

HORIZONTAL Installation

VERTICAL Installation

Drain Connection

Air Flow Balancing

Balancing Procedure

Outlines the general steps and prerequisites for balancing air flows in HRV/ERV units.

Pitot Tube Airflow Balancing

Details the method of field balancing using a Pitot tube and Magnehelic gauge.

Maintenance

Regular Maintenance

Covers routine cleaning and checks for the unit.

Troubleshooting