Outdoor fan speed is defined by operation mode.
and RP1724/1730HJVXA fan speed is defined
by outdoor temperature zone.
Cooling (D zone) Heating
RP1724HJVXA
RP1730HJVXA
F zone
900/ 850/ 800/
620/ 550/ 450
(rpm)
G zone H zone
500/ 320/ 250 300/ 230/ 200 220/ 200
850 / 800 / 620 /
500 / 400
Dry
Low outdoor temperature cooling / dry
550/ 450
900/ 850/ 800/
620/ 550/ 450
500/ 320/ 250 300/ 250/ 200 220/ 200
850 / 800 / 620 /
500 / 400
550/ 450
Outside air temperature zone selection
53.6°F
(12°C)
32°F
( 0°C)
Outside air
temperature
Outside air
temperature
F zone
D zone
G zone
H zone
35.6°F
(2°C)
17.6°F
(-8°C)
50°F
(10°C)
14°F
( -10°C)
04-15
Cooling Heating
RP1736HJVXA
RP1748HJVXA
(rpm)
890/ 830/ 710/ 640/
580/ 520/ 460/ 390/
340/ 290
910/ 830/ 710/ 640/
580/ 520/ 460/ 390/
340/ 290