11. DEFROST OPERATION CONTROL
1. CONDITION OF STARTING DEFROST OPERATION
Condition
2. CONDITION OF THE DEFROST OPERATION COMPLETION
Defrost operation is released when conditions become as below.
RP1724/1730HJVXA
RP1736/1748HJVXA
Outdoor condenser coil temperature is higher than 59.0°F (15°C)
or Compressor operation time has passed 15 minutes.
Outdoor condenser coil temperature is higher than 55.4°F (13°C)
or Compressor operation time has passed 15 minutes.
Defrost operation starts as below.
RP1724, 30HJVXA,
Condition
Less than
35 minutes
More than 35 minutes
Does not work
Compressor
integrating
operation time
RP1724/1730HJVXA
(1st defrost after starting operation)
Condition
Less than
17 minutes
More than 17 minutes More than 57 minutes
Does not work
Compressor
integrating
operation time
Integrating (OFF count) defrost operation
RP1724/1730HJVXA
(2nd defrost or later after staring operation)
Compressor
integrating
operation time
Tn -13°F (-25°C)
Tn - Tn10 < 9°F (-5°C) ( Tn 21.2°F (-6°C))
Tn - Tnb < -3.6°F (-2°C) ( Tn 21.2°F (-6°C))
Tn : Outdoor condenser coil temperature.
Ta : Outside temperature.
Tn10 : Temperature of continuous operation at 10 minutes.
Tnb : Back 5 minutes temperature.
More than 210 minutes
(For long continuous operation)
Condition
More than 210 minutes
( For long continuous operation
)
(and after 30 minutes, if 26.6°F (-3°C)) (and after 5 minutes, if 23°F (-5°C))
(and after 5 minutes, if 23°F (-5°C))
Compressor
integrating
operation time
Less than 10 minutes
(For intermittent operation)
OFF count of compressor : 40 times
If compressor continuous operation time
is less than 10 minutes,
the OFF number of the compressor is counted.
If any defrost operated,
the compressor OFF count is cleared.
(and after 5 minutes, if 41°F (5°C))
Ta - Tn 41°F (5°C)
and
Tn 15.8°F (-9°C)
Tn 26.6°F (-3°C) Tn 23°F (-5°C)
Tn 23°F (-5°C)
04-25
Less than 35 minutes More than 35 minutes
Does not operate
Normal defrost
RP1736/1748HJVXA
Tn 1.4°F (-17°C)
(at Ta
°F
Tn - Tn-1
Compressor integrating operation time
<
=
>
=
14°F (-10°C)
Tn 0.8 x Ta-11.6 or Tn -18.4 (-28°C)
<
=
<
=
(at 4°F (-20°C)
<
=
Ta< 14°F (-10°C)
°FTn 0.8 x Ta-11.6 or Tn -18.4 (-28°C)
<
=
<
=
(at Ta < 4°F (-20°C))
< 28.4°F (-2°C)
(Tn 21.2°F (-6°C))
Tn : Outdoor condenser coil temperature.
Ta : Outside temperature.
Tn-1 : Before 5 minutes detected Tn.
Condition of Integrating defrost operation