4. Capacity table
Capacity tables show each of following values calculated based on the outdoor temperature and the
indoor temperature, under given Airflow Rate (AFR):
For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP)
For heating capacity: Total Capacity (TC) and Input Power (IP)
4-1. Cooling capacity
¢ Model: RHMV2421MNACJA
AFR CFM 800
Indoor temperature
°FDB 64 70 75 80 85 90
°FWB 54 60 63 67 71 73
Outdoor temperature
°FDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kBtu/h kW kBtu/h kW kBtu/h kW kBtu/h kW kBtu/h kW kBtu/h kW
-5 5.43 5.43 2.54 5.66 5.66 2.67 6.05 6.05 2.74 6.45 6.45 2.88 7.55 7.55 2.90 8.10 8.10 2.92
5 10.89 10.89 1.99 11.17 11.17 2.12 11.85 11.85 2.20 12.94 12.94 2.26 14.37 14.37 2.29 16.24 16.24 2.29
14 14.98 13.21 1.60 16.05 13.59 1.72 17.10 14.24 1.81 18.27 15.24 1.89 19.50 16.44 1.94 20.90 18.03 1.97
32 20.95 16.64 1.06 23.21 17.15 1.18 24.81 17.77 1.28 26.10 18.62 1.37 27.07 19.51 1.45 27.78 20.66 1.53
41 22.83 17.73 0.92 25.49 18.29 1.04 27.27 18.91 1.13 28.62 19.69 1.23 29.50 20.51 1.32 30.00 21.51 1.41
50 23.97 18.41 0.87 26.89 19.01 0.98 28.80 19.63 1.07 30.19 20.35 1.16 31.04 21.14 1.25 31.40 22.06 1.35
59 24.37 18.68 0.91 27.42 19.31 1.01 29.40 19.94 1.09 30.83 20.60 1.18 31.67 21.41 1.26 32.00 22.29 1.35
67 24.12 18.58 1.02 27.17 19.22 1.10 29.17 19.86 1.17 30.61 20.48 1.25 31.48 21.35 1.33 31.85 22.23 1.41
77 22.97 17.98 1.25 25.88 18.64 1.31 27.83 19.30 1.37 29.29 19.86 1.43 30.24 20.87 1.49 30.74 21.82 1.56
86 21.16 17.02 1.54 23.81 17.67 1.60 25.65 18.36 1.64 27.11 18.87 1.68 28.17 20.06 1.72 28.90 21.11 1.76
95 18.61 15.64 1.93 20.86 16.27 1.96 22.54 17.00 1.98 24.00 17.48 2.00 25.20 18.88 2.01 26.24 20.10 2.02
104 15.32 13.85 2.40 17.05 14.46 2.41 18.50 15.22 2.42 19.95 15.67 2.43 21.34 17.35 2.44 22.77 18.78 2.45
115 10.31 10.31 3.10 11.21 11.21 3.11 12.32 12.32 3.12 13.74 12.90 3.12 15.40 14.99 3.13 17.43 16.74 3.14
AFR
m
3
/h
1,359
Indoor temperature
°CDB 17.8 21.1 23.9 26.7 29.4 32.2
°CWB 12.2 15.6 17.2 19.4 21.7 22.8
Outdoor temperature
°CDB
TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP
kW kW kW kW kW kW
-20.6 1.59 1.59 2.54 1.66 1.66 2.67 1.77 1.77 2.74 1.89 1.89 2.88 2.21 2.21 2.90 2.37 2.37 2.92
-15 3.19 3.19 1.99 3.27 3.27 2.12 3.47 3.47 2.20 3.79 3.79 2.26 4.21 4.21 2.29 4.76 4.76 2.29
-10 4.39 3.87 1.60 4.71 3.98 1.72 5.01 4.17 1.81 5.35 4.47 1.89 5.72 4.82 1.94 6.13 5.28 1.97
0 6.14 4.88 1.06 6.80 5.03 1.18 7.27 5.21 1.28 7.65 5.46 1.37 7.93 5.72 1.45 8.14 6.06 1.53
5 6.69 5.20 0.92 7.47 5.36 1.04 7.99 5.54 1.13 8.39 5.77 1.23 8.65 6.01 1.32 8.79 6.31 1.41
10 7.03 5.40 0.87 7.88 5.57 0.98 8.44 5.75 1.07 8.85 5.96 1.16 9.10 6.20 1.25 9.20 6.46 1.35
15 7.14 5.47 0.91 8.04 5.66 1.01 8.62 5.84 1.09 9.04 6.04 1.18 9.28 6.28 1.26 9.38 6.53 1.35
19.4 7.07 5.44 1.02 7.96 5.63 1.10 8.55 5.82 1.17 8.97 6.00 1.25 9.23 6.26 1.33 9.33 6.52 1.41
25 6.73 5.27 1.25 7.59 5.46 1.31 8.16 5.66 1.37 8.58 5.82 1.43 8.86 6.12 1.49 9.01 6.39 1.56
30 6.20 4.99 1.54 6.98 5.18 1.60 7.52 5.38 1.64 7.95 5.53 1.68 8.26 5.88 1.72 8.47 6.19 1.76
35 5.45 4.58 1.93 6.11 4.77 1.96 6.61 4.98 1.98 7.03 5.12 2.00 7.39 5.53 2.01 7.69 5.89 2.02
40 4.49 4.06 2.40 5.00 4.24 2.41 5.42 4.46 2.42 5.85 4.59 2.43 6.25 5.09 2.44 6.67 5.50 2.45
46.1 3.02 3.02 3.10 3.29 3.29 3.11 3.61 3.61 3.12 4.03 3.78 3.12 4.51 4.39 3.13 5.11 4.91 3.14
- 8 -
4-1. Cooling capacity 4. Capacity table
DUCT TYPE
RHMV2421-4821*NACJ
A
DUCT TYPE
RHMV2421-4821*NACJ
A