Installation configuration of individual connection
External heating device is installed individually. (No use of indoor unit fan)
Example of heating device:
- Floor heating device
On/Off
WARNING
DIP Switch 101-3 must be in the ON position when ducted electric heat application is be-
ing used. DIP switch 101-3 is set in the ON position by default from the factory. When DIP
switch 101-3 is in the ON position and ducted electric heat application is not being used, cold
draft occurs due to fan delay off operation.
Operation Condition
Heater off
DIP-SW101-3 On Heater is off as shown in following diagram of heating
temperature.
Other than heating mode
Error occurred
Forced thermostat off
Fan stop protection
Indoor unit fan
setting for
external heater
Enabled
DIP-SW101-3 Off Heater is off as shown in following diagram of heating
temperature.
Other than heating mode
Error occurred
Forced thermostat off
Indoor unit fan
setting for
external heater
Disabled
CN65CN47 CN5
CN48
SW101
Design and install external heater appropriately with considering its protection.
External
heater
Indoor
unit
Supply air Return air
Inappropriate designing and installation of external heater may cause a fire by emitted heat from
the external heater.
- 35 -
7-4. Details of function 7. External input and output
DUCT TYPE
RHMV2421-4821*NACJ
A
DUCT TYPE
RHMV2421-4821*NACJ
A