EasyManua.ls Logo

Rheem RP1748HJVXA - Page 44

Rheem RP1748HJVXA
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation status
On
On
12 V
Off
Off
0 V
Heater
Comp. On/Off
Outdoor temperature
(Factory setting)
Outdoor temperature zone*
Heat pump
prohibition
zone
Heat pump
only zone
Combination zone
*: The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min.
46.4°F (8°C)
42.8°F (6°C)
-0.F (-1C)
-4°F (-20°C)
On
Off
Fan
DIP-SW101-3: On
DIP-SW101-3: Off
NOTE: In following operations, compressor will be on in heat pump prohibition zone.
Other than heating
Test run
- 40 -
7-4. Details of function 7. External input and output
DUCT TYPE
RHMV2421-4821*NACJ
A
DUCT TYPE
RHMV2421-4821*NACJ
A

Table of Contents

Other manuals for Rheem RP1748HJVXA

Related product manuals