Type
Duct
Inverter heat pump
Model name RHMV2421MNACJA RHMV3021SNACJA RHMV3621MNACJA RHMV4821SNACJA
Operation range
Cooling
°F (°C) 64 to 90 (18 to 32)
%RH 80 or less 80 or less
Heating °F (°C) 60 to 86 (16 to 30)
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 80 °FDB/67 °FWB (26.67 °CDB/19.44 °CWB), and outdoor temperature of 95 °FDB/75 °FWB (35 °CDB/23.9 °CWB).
Heating: Indoor temperature of 70 °FDB/59 °FWB (21.11 °CDB/15 °CWB), and outdoor temperature of 47 °FDB/43 °FWB (8.33 °CDB/6.11 °CWB).
Pipe length: 24 ft 7 in (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
Standard static pressure: 0.18 in.WG (45 Pa): 24 model, 0.23 in.WG (58 Pa): 30, and 36 model, 0.28 in.WG (70 Pa): 48 model
Protective function might work when using it outside the operation range.
*1: Maximum current:
The maximum value when operated within the operation range.
The total current of indoor unit and outdoor unit.
*2: Sound pressure level:
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.