Type Inverter heat pump
Model name RP1736HJVXA RP1748HJVXA
Power supply 208/230 V ~ 60 Hz
Power supply intake Outdoor unit
Available voltage range 187—253 V
Starting current A 20.1
Fan
Airflow rate
Cooling
CFM (m
3
/h)
2,590 (4,400)
Heating 2,590 (4,400)
Type × Q'ty Propeller × 1
Motor output W 111
Sound pressure level *
Cooling
dB (A)
53 54
Heating 54 55
Condenser coil type
Dimensions
(H × W × D)
in 38-1/16 × 36-5/16 × 2-3/16
mm 966 × 922 × 55
Fin pitch FPI 18
Rows × Stages 3 × 46
Pipe type Copper
Fin
Type (Material) Aluminum
Surface treatment Blue Fin
Compressor
Type × Q'ty DC twin rotary × 1
Motor output W 2,100
Refrigerant
Type R410A
Charge
lb oz 9 lb 8 oz
g 4,300
Refrigerant oil
Type POE (RB68)
Amount
in
3
(cm
3
)
70.2 (1,150)
Enclosure
Material Steel
Color
Beige
Approximate color of Munsell 10YR 7.5/1.0
Dimensions
(H × W × D)
Net in (mm)
39-5/16 × 38-3/16 × 14-9/16
(998 × 970 × 370)
Gross in (mm)
45-12/16 × 41-14/16 × 18-13/16
(1,162 × 1,064 × 478)
Weight
Net
lb (kg)
198 (90)
Gross 220 (100)
Connection pipe
Size
Liquid
in (mm)
Ø3/8 (9.52)
Gas Ø5/8 (15.88)
Method Flare
Pre-charge length
ft (m)
98 (30)
Max. length 230 (70)
Max. height difference 98 (30)
Operation range
Cooling
°F (°C)
14 to 115 (-10 to 46)
Heating -4 to 75 (-20 to 24)
Drain hose
Material LDPE
Size in (mm) Ø1/2 (13.0) [I.D.], Ø5/8 to Ø11/16 (16.0 to 16.7) [O.D.]
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) / 67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB).
Heating: Indoor temperature of 70 °FDB (21.11 °CDB) / 59 °FWB (15 °CWB), and outdoor temperature of 47 °FDB (8.33 °CDB) / 43 °FWB (6.11 °CWB).
Pipe length: 24 ft 6 in (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*: Sound pressure level
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.