11
454107.66.01-02_GB
01.07.2015
Translation of the Original
4. TRANSPORT AND STORAGE
The safety notices contained in Chapter 1 must be complied with !
The in-house transport is carried out by a forklift, lift truck or crane.
The process cooler must be placed on a level surface in order to prevent any distortion of the
base frame.
4.1 Transport Specifications
- Weight see Technical Data
- Main dimensions see Appendix
- Ambient temperatures -25 °C to + 50 °C
- Relative humidity 10% to 90% rel. humidity
- Air pressure 70 -106 kPa
4.2 Indoor Units 2NK6 746W (10589726) and 2NK6 745-1W (10430821)
The indoor unit of the split cooling system is designed exclusively for installation in enclosed
and sheltered areas. The unit must not be installed outdoors as it cannot be guaranteed that
the unit will function properly there (temperature effect, tightness of the housing).
The surface must be even, level and horizontal. For the installation of the „Seismic-Kit“ an
additional hole needs to be dsrilled into the ground.
(see Installation Instructions, GDD number 454107.66.02).
To guarantee proper accessibility for the performance of maintenance and service work, the
following minimum clearances need to be maintained:
4. Transport and Storage
ENGLISH