2094
6
GB
COMBUSTION ADJUSTMENT
In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjustment
and testing must be carried out observing the instruction manual of the boiler, including verification of
the CO and CO
2
concentration in the flue gases, their temperatures and the average temperature of
the water in the boiler.
To suit the required appliance output, choose the proper nozzle and adjust the pump pressure, the set-
ting of the combustion head, and the air damper opening in accordance with the following schedule.
The values shown in the table are measured on a CEN boiler (as per EN 303).
They refer to 12.5% CO
2
at sea level and with light oil and room temperature of 20 °C.
RECOMMENDED NOZZLES : Monarch type R ; Delavan type W - B
Steinen type S - Q ; Danfoss type S - B
PUMP PRESSURE: 12 bar : The pump leaves the factory set at this value.
14 bar : Improves flame-retention; it is therefore suitable for ignitions
at low temperatures.
COMBUSTION HEAD SETTING
This is done when fitting the nozzle, with the blast tube removed. It depends on the output of the
burner and is carried out by rotating the regulating rod, till the terminal plane of the blast tube is level
with the set-point, as indicated in the schedule.
Nozzle Pump
pressure
Burner
output
Comb. head
adjustment
Air damper
adjustment
GPH Angle bar kg/h ± 4% Set-point Set-point
1.10 60° 12.5 4.5 2 3.2
1.25 60° 12 5.0 2.5 4.5
1.50 60° 12 6.0 3 6
1.75 60° 12 7.0 4 6.5
2.00 60° 12 8.0 5 7
2.00 60° 15 9.0 6 8
In the sketch on the left below, the
combustion head is set for an output
of 1.50 GPH at 12 bar, while the
shutter is level with set-point 3, as
required by the above table.
Blast tube
Regulating rod
Shutter
Terminal plane of the blast tube
D5398
2
135