APPENDIX
APPENDIX G - BOILER INSTALLATION (EXAMPLE DRAWINGS)
Array AR 3000 / AR 4000 Single Unit Installation
SECONDARY
SUPPLY SENSOR
(MANDATORY)
PRESSURE
REDUCING
VALVE
EXPANSION TANK
SYSTEM
CIRCULATOR
SYSTEM
RETURN
SECONDARY
SYSTEM
SUPPLY
DIRT TRAP
MANUAL
SHUTOFF
VALVE
GAS
PRESSURE
REGULATOR
MAINTAIN A RECOMMENDED
8" W.C. PRESSURE (MINIMUM
4.0" W.C.) AT HIGH-FIRE INPUT
GAS
SUPPLY
CONDENSATE
DRAIN PIPE
RELIEF VALVES
DRAIN PIPE
SUPPLY
(Boiler Outlet)
RETURN
(Boiler Inlet)
COMBUSTION AIR
FLUE
AIR ELIMINATOR
MANDATORY
BOILER
STRAINER
PRESSURE
GAUGE
COMMON PIPE DIAMETER MUST BE
SIZED FOR FLOW RATES LESS THAN
4.0 FT/SEC. COMMON PIPE LENGTH
BETWEEN THE CLOSE TEES MUST BE
3 TO 5 TIMES ITS DIAMETER
1.
THIS DRAWING IS MEANT TO DEMONSTRATE SYSTEM PIPING CONCEPT
ONLY.
2.
INSTALLATIONS MUST COMPLY WITH ALL LOCAL CODES.
3.
INSTALL A MINIMUM OF 12 DIAMETERS OF STRAIGHT PIPE UPSTREAM
OF ALL CIRCULATORS.
4.
INSTALL A MINIMUM OF 6 DIAMETERS OF OF STRAIGHT PIPE UP AND
DOWNSTREAM OF ALL CLOSELY SPACED TEES.
5.
PIPING SHOWN IS PRIMARY/SECONDARY.
6.
RECOMMENDED (AND REQUIRED WHEN SUPPLY PRESSURE IS
GREATER THAN 20" W.C.): GAS PRESSURE REGULATOR
(LEVER-ACTING, POSITIVE-LOCKUP TYPE WITH OVER-PRESSURE
PROTECTION (INTERNAL RELIEF).
7.
MANDATORY: BOILER STRAINER (20 MESH OR FINER).
8. THE CONDENSATE DRAIN TUBE MUST PITCH AWAY FROM THE BOILER
(1/4” SLOPE PER FOOT) AND MUST NEVER REDUCE ITS DIAMETER
DOWNSTREAM
10 ft recommended