EasyManua.ls Logo

Riello G20 - Burner Start-up Cycle and Flame Detachment

Riello G20
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2903443
22
GB
Start-up, calibration and operation of the burner
8.8 Burner start-up cycle
8.9 Adjustments, to avoid flame - detachment, at burner - ignition (only for gas oil)
CORRECT POSITIONING OF THE ELECTRODES
Refer to Fig. 22 at page 21.
PUMP - SETTING
When the temperature of the gas oil decreases below +5 °C, in-
crease the pressure to 14 bar.
NOZZLE: ATOMIZING ANGLE
Choose 60° nozzle.
COMBUSTION HEAD ADJUSTMENT
Regulate the combustion head one set-point further ahead than
indicated in the instructions.
Example: the instructions require to set the combustion-head on
set-point 3.5. Instead, the setting is made on set-point 4.5.
FAN - AIR DAMPER ADJUSTMENT
Adjust the damper, reducing the excess air until the Bacharach
number is not near 1. (i.e. a combustion with the lowest possible
excess-air).
Thermostat
Motor
Ignition transformer
Valve
Flame
Lock-out lamp
~
12s
D5229
~
12s
~
5s
Lock-out due to failure to lightNormal
Fig. 23