LED indicator and special function
9.4 LED lamps: burner operating status
OPERATING STATUSES INDICATED BY LEDS DURING NORMAL OPERATION AND CHECK MODE
Tab. N
1. LEDs form a progress bar which indicates the Flame Signal
Power in order to orientate the sensors during commissioning
(LEDs “Grow” upwards, moving away from the Status at 20%
intervals of flame power.)
2. LEDs indicate the error or lock-out code for troubleshooting.
3. LEDs change from ON to BLINKING to OFF showing the
servomotor movement control until the position-reached
feedback is received see paragraph “Problems - Causes -
Remedies signalled by LED indicators” on page 34“.
Operation
LED ● = ON
Fan
Damper
open
Damper
closed
Modulation Ignition Flame Status
Icon
Power OFF/ON OFF
Not ready/
Diagnostics
Green
Standby Green
Servomotor
movement
(Note 3)
OFF
Flashing
Flashing
OFF
Green
Waiting for closing Green
blinking
Green
OPEN
(before ignition)
Green
Minimum
(before ignition)
Green
Ignition Green
PTFI
Green
blinking
Green
MTFI Green
Active modulation Green
Minimum output
position
Green
With flame present Green
Economy mode Green
Check during maximum
opening phase
Flashing Yellow
Check during minimum
closing phase
Flashing Yellow
Check during ignition
phase with pilot PTFI
Flashing ● Note 1 ● Note 1 ● Note 1 ● Note 1 ● Note 1 Yellow
Check during ignition
phase with main fuel
valve MTFI
Flashing ● Note 1 ● Note 1 ● Note 1 ● Note 1 ● Note 1 Yellow
Fault/lock-out ● Note 2 ● Note 2 ● Note 2 ● Note 2 ● Note 2 ● Note 2 Red
End of the cycle Green
S9740
S9741
S9742
S9743
S9744
S9745
S9746