35
20166443
GB
Problems - Causes - Remedies signalled by LED indicators
Error / RFGO LED lock-out codes
No Faults LED 1 LED 2 LED 3 LED 4 LED 5 LED 6 LED 7
Operation
LED ● = ON
Fan
Open
damper
Closed
damper
Auto Ignition Flame Status
Icon
1 Post-diagnostics fault Red
2 Local reset Red
3 Combustion air fan fault Red
4 Supervisor processor diagnostics fault Red
5
FR- NO Flame at the end of the 2
nd
safety time (MTFI)
Red
6 FR: internal circuit fault Red
7 Internal communication fault Red
8 Remote reset Red
9 FR: internal fault Red
10 Main processor fault Red
11 Data memory test fault Red
12 Data memory test fault Red
13 Mains voltage or frequent fault Red
14 Internal processor fault Red
15 Internal processor fault Red
16
No flame: 1
st
safety time (PTFI)
Red
17 Wiring fault Red
18 Safety relay fault Red
19 Combustion airflow switch fault in the
rest position
Red
20
UV: no flame at the end of the 2
nd
safety time (MTFI)
Red
21 Safety relay fault Red
22 Supervisor processor fault Red
23 Supervisor memory test fault Red
24 Flame loss during the operation
(AUTO)
Red
25 Supervisor processor data memory
fault
Red
26 Supervisor processor internal fault Red
27 Not used
28 Not used
29 Operating temperature out of range Red
30 Code memory fault Red
31 FR: external short circuit Red
32 Check mode timeout (manual) Red
33 False flame in stand-by mode Red
34 Not used
35 Internal processor timeout Red
36 Internal processor timeout Red
37 Combustion air check timeout Red
38 Internal processor timeout Red
39 Internal processor timeout Red
40 Internal hardware fault Red
41 Internal hardware fault Red
42 Main processor fault Red
43 Supervisor processor fault Red
44 Supervisor processor timeout Red
45 Off-specification mains voltage Red
S9740
S9741
S9742
S9743
S9744
S9745
S9746

Related product manuals