Polypropylene (PP) Common Venng Installaon Instrucons 5
• High altude installaons are cered up to 10,200 (3,109 m).
• Reference the respecve Rinnai Tankless Water Heater Installaon and Operaon Manual to set the water heater
for the altude at which they will be operang.
• Tankless water heaters using common venng at altudes over 2,000 will automacally derate.
• Unless recovering a tank, Rinnai recommends electronically connecng with common venng and where water
heaters are in a manifold system. Refer to the Rinnai Tankless Water Heater Installaon and Operaon Manual for
addional details on electronically connecng mulple water heaters.
• Mul-story and common venng systems are allowed. Such venng system shall be in accordance with the
Naonal Fuel Gas Code, ANSI Z223.1/NFPA54 and/or the CSA B149.1, Natural Gas and Propane Installaon Code
(Current Edion), local codes, and the manufacturer's instrucons. Refer to "Vercal Common Venng System
Installaon Instrucons" for addional informaon. Refer to the appendix of this manual for Ubbink vent
component assembly and installaon instrucons.
Informaon
For the table on next page:
Header is the main vent pipe into which several vents connect. Vent Length is the distance from the end of the header
to the vent terminaon. Maximum vent length starts at the end of the header system. Use 10 (3 m) as equivalent
vent length for 90° elbows. For use with SENSEI™ internal (indoor) tankless water heaters.
Header
Vent Length