16
008082013GW
This can occur on a Q Boiler when the factory
jumper on the flue gas sensor is loose or has
fallen out.
212˚F is the default temperature setting for
parameter 84. Verify to see if the temperature
setting for this parameter is set higher than
the default. If so, inspect vent system for
blockage.