8 Value Series Manual
24"
V
Check on whether local codes supersede these clearances.
Avoid terminaon locaons near a dryer vent.
Avoid terminaon locaons near commercial
cooking exhaust.
You must install a vent terminaon at least 12
inches from the ground
60"
V
V
(1.52 m)
between
terminals at
dierent levels
(0.61 m) to wall or parapet
(0.30 m) between
terminals at same
level
12"
V V
(1.52 m) vercally
between terminals
V
60"
V
Addional clearances - V75i, V65i
12"
12"
36"
INSIDE
CORNER
V V
(0.30 m ) to
an inside
corner
(0.30 m) between
terminals at same
level
Important consideraons for locang vent
terminaon under a sot (venlated or unvenlated
or eave vent; or to a deck or porch)
Do not install vent terminaon under a sot vent
such that exhaust can enter the sot vent
Install vent terminaon such that exhaust and
rising moisture will not collect under
eaves. Discoloraon to the exterior of the
building could occur if installed too close.
Do not install the vent terminaon too close
under the sot where it could present
recirculaon of exhaust gases back into the
combuson air intake part of the terminaon

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rinnai V75i series and is the answer not in the manual?

Rinnai V75i series Specifications

General IconGeneral
TypeTankless Water Heater
Fuel TypeNatural Gas or Propane
Maximum BTU180, 000 BTU
Flow Rate7.5 GPM
Energy Factor0.82
InstallationIndoor
Gas Connection3/4" NPT
Water Connection3/4" NPT
BTU Input Range15, 000 - 180, 000 BTU
Temperature Range98°F to 140°F
Electrical Requirements120V AC, 60Hz
Ignition TypeElectronic
Warranty5-year on parts, 1-year on labor