PG 4
Celsius
jumper
Reset
button
Aux Only
Heat Pump
Customer Support: 877-505-2353 Visit our webiste
www.ritetemp-thermostats.com
1611-010
F
0
/ C
0
Select
The F/C jumper is under the top cover Jumper #5. It determines which
temperature system is displayed on the LCD display. With the jumper off, the
display is Fahrenheit (default setting), with the jumper on both pins, the
display is Centigrade. When the jumper is changed, the unit must be reset
(under the top cover on the left).
Low Battery
When the batteries are low, the battery icon will flash. The two AAA
batteries in the unit need to be replaced. The HVAC system will stop
functioning when the thermostat loses power; replace batteries as soon
as you see this warning. Press RESET after replacing batteries
If you have a heat pump with auxiliary heat, and the heat pump is not
working, you can use the auxiliary heat only by moving jumper 1 [heat pump]
to jumper position 2 [ Aux only].
1
2
3
4
5
6
7
To set a Heat Pump's Aux only mode