5. Parameters
XM670K
16
Instructions for useRev.v. 01
|
9600- 0099
|
© 2022 RIVACOLD srl
5.1.8
Energy saving
Parameter
Description
Values/Range
ESP
Energy-saving probe selection.
nP, P1, P2, P3
HES
Temperature increase during energy-saving cycle. Determines by how much the set
point increases or decreases during the energy-saving cycle.
- 30.0°C...
30.0°C
- 54...54°F
PEL
Activation of energy saving together with light switch-off: n= function disabled. Y=
energy saving activated at light switch-off and vice versa.
n, Y
5.1.9
LAN network management
Parameter
Description
Values/Range
LdS
Display synchronisation: y= The value shown on the local section display is also sent to
all other sections. n= The value is only shown on the local display.
y, n
LSd
Remote probe display: y= Enables the display of the value measured by a remote probe
(sent from a section with parameter LdS= 1). n= Displays the value of one of the local
probes.
y, n
5.1.10
Read-only service
Parameter
Description
Values/Range
CLt
Cold call percentage: shows the actual cooling time calculated by XM670 during
adjustment.
-
tMd
Time remaining until next defrosting (tens of seconds): shows the time before the next
defrosting if interval defrosting is selected.
-
LSn
Number of LAN Sections: displays the number of sections available in the local
network.
1...5
LAn
Serial address in LAN: identifies the address of the instrument within the local
network of the ducted counter.
1...LSn
Adr
Serial address: identifies the serial address of the instrument when connected within
a Modbus serial network.
1…247
rEL
Software version: (read-only) shows the software version of the microprocessor.
-
Ptb
Parameter Table: (read-only) shows the original code of the parameter map.
-
Pr2
Second-level menu access (read-only).
-