Instructions for useRev.v. 01
|
9600- 0099
|
© 2022 RIVACOLD srl
2.2.3
Display recorded temperatures
1.
Press the button.
2.
Scroll down the menu to the label L°t and press SET to see the lowest recorded temperature, press
SET on the H°t label to display the maximum recorded temperature.
2.2.4
Display and change set point
1.
Press the SET button for approx. 3 s: the set point value is displayed. The unit of measurement icons
flash.
2.
Change the SET value by using the or buttons.
3.
Press the SET button again to store the value.
2.2.5
Enabling the manual defrosting cycle
Press the defrosting button for more than 3 seconds.
Note: Only if the conditions are present (i.e. if the value of probe P2 is below the value of dtE).
2.2.6
Enter the PR1 programming menu
Press the SET + button combination for a few seconds. The units start flashing and the instrument
displays the label of the first parameter present.
2.2.7
Changing the value of a parameter
1.
Enter parameter programming.
2.
Press the SET button to display the parameter value (units start flashing).
3.
Press or to set the parameter.
4.
Press the SET button to store the value and move to the next parameter.
Note: The new programming is stored even if you exit the programming phase by time-out.
2.2.8
OFF Status
By pressing the button , the instrument displays “OFF”. In this situation, all relays are deactivated
and the control is switched off. If a monitoring system is connected, it will not record any valid data or
alarm situations.
Note: In the OFF state, the light relay is active.