154 Direct Digital Controller fw 4.013 – Ed. 01/2013
with error E1029. The error clears when the cause generating it is removed.
E1046
C(H) OUT T Prb Malf (2-line Cooling or Cooling/Heating Plant Delivery Probe Malfunction)
See description E 1045
E1047
H IN T Probe Malf (Heating Plant Return Probe Malfunction)
See description E 1045.
E1048
H OUT T Probe Malf (Heating Plant Delivery Probe Malfunction)
See description E 1045.
E1049
Sep IN T Prb Malf (Separable Plant Part Return Probe Malfunction)
This error is generated in the event of an error or absence on the probe in question.
The error halts the system (the generators are switched off) if the DDC uses this probe to regulate the plant; in
this case it is present together with error E1030. The error clears when the cause generating it is removed.
E1050
Sep OUT T Prb Malf (Separable Plant Part Delivery Probe Malfunction)
See description E 1049.
E1051
GAHP IN T Prb Malf (Heat Pump Return Probe Malfunction)
See description E 1045.
E1052
Pri W Pump C® Offlin (2 line Cooling or Cooling/Heating Plant Primary Water pump Offline)
This error is generated if communication between the DDC and the RB200 managing the water pump in
question is interrupted.
The error may also be generated when updating the RB200 and/or reconfiguring the module managing the
water pump, not followed by a new "machine configuration" on the DDC.
The error halts the system (the generators are switched off). The error clears off in the event of a
communication reset or completion of the configuration, depending on the cause which generated it.
E1053
H Prim W Pump Offline (Heating Plant Primary Water pump Offline)
See description E 1052.
E1054
Sep Pri W Pump Offline (Separable Plant Part Primary Water pump Offline)
See description E 1052.
E1055
C(H) Pri W Pump Conflt (2-line Cooling or Cooling/Heating Plant Primary Water pump Configuration
Conflict)
The error is generated in the event that another device with the same ID is configured on the communication
network.
This error does not halt the system.
E1056
H Prim W Pump Conflt (Heating Plant Primary Water pump Configuration Conflict)
See description E 1055.
E1057
Sep Prim W Pump Conflt (Separable Plant Part Primary Water pump Configuration Conflict)
See description E 1055.
E1058
Base Man Prb not cfg (Base Plant Part Manifold Probes not Configured)
This error is generated if the base plant part manifold probes have not been configured on an RB200 device,
and these probes are required by the DDC to regulate the plant (i.e. presence of third party modules on the
base plant part). When using the progressive complement and substitution mode, the error is also generated if
the probe on the GAHP unit return manifold has not been configured.
The error halts the system (the generators are switched off). The error clears when the configuration is
corrected.
E1059
Sep Man Prb not cfg (Separable Plant Part Manifold Probes not Configured)
This error is generated if the separable plant part probes have not been configured on an RB200 device, and
these probes are required by the DDC to regulate the plant (i.e. presence of third party modules on the
separable plant part).
The error halts the system (the generators are switched off). The error clears when the configuration is
corrected.
E1060
Base W Pump not config (Base Plant Part Water pump not Configured)
This error is generated if the base plant part water pump has not been configured on an RB200 device, and
this water pump is required to operate the plant (i.e. third party modules without water pump control on the
base plant part, with the exception of the case below for managing independent water pumps and manifold