Direct Digital Controller
Direct Digital Controller fw 4.013 – Ed. 01/2013 155
probes on the secondary circuit, which does not require this water pump).
The error halts the system (the generators are switched off). The error clears when the configuration is
corrected.
E1061
Sep W Pump not config (Separable Plant Part Water pump not Configured)
This error is generated if the separable plant part water pump has not been configured on an RB200 device,
and this water pump is required to operate the plant (i.e. third party modules without water pump control on
the separable plant part).
The error halts the system (the generators are switched off). The error clears when the configuration is
corrected.
E1062
C(H) Sec W Pump Offlin (2 line Cooling or Cooling/Heating Plant Secondary Water pump Offline)
This error is generated if communication between the DDC and the RB200 managing the water pump in
question is interrupted.
The error may also be generated when updating the RB200 and/or reconfiguring the module managing the
water pump, not followed by a new "machine configuration" on the DDC.
The error halts the system (the generators are switched off). The error clears off in the event of a
communication reset or completion of the configuration, depending on the cause which generated it.
E1063
H Secon W Pump Offline (Heating Plant Secondary Water pump Offline)
See description E 1062.
E1064
C(H) Sec W Pump Conflt (2-line Cooling or Cooling/Heating Plant Secondary Water pump
Configuration Conflict)
The error is generated in the event that another device with the same ID is configured on the communication
network.
This error does not halt the system.
E1065
H Secon W Pump Conflt (Heating Plant Secondary Water pump Configuration Conflict)
See description E 1064.
Table 7– OPERATING ANOMALY CODES
To carry out an error reset consult Paragraph 2.7 “Error reset” on Page 17 and Paragraph 2.8 “FLAME
CONTROL UNIT RESET” on Page 18.
It is not possible to Reset Errors or Reset the Flame Unit on third party modules.
NOTE