• install the MicroLogix 1100 system in a properly rated (NEMA) enclosure. Make sure 
that the MicroLogix 1100 system is properly grounded.
• use Belden cable #8761 for wiring the analog channels, making sure that the drain 
wire and foil shield are properly earth grounded.
• route the Belden cable separately from any ac wiring. Additional noise immunity can 
be obtained by routing the cables in grounded conduit.
Grounding Your Analog Cable
Use shielded communication 
cable (Belden #8761). The Belden 
cable has two signal wires (black 
and clear), one drain wire, and a 
foil shield. The drain wire and foil 
shield must be grounded at one 
end of the cable.  
Do not ground the drain wire and foil shield at both ends of the cable.
Foil Shield
Black Wire
Drain Wire
Clear Wire
Insulation