EasyManua.ls Logo

Rockwell Automation 440R-D22R2

Rockwell Automation 440R-D22R2
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
80 Rockwell Automation Publication 440R-UM013F-EN-P - July 2021
Appendix A Specifications
Single Wire Safety (SWS) Specifications
Attribute 440R-S13R2 (CI) 440R-D22R2 (DI) 440R-D22S2 (DIS) 440R-EM4R2 (EM) 440R-EM4R2D (EMD) 440R-S12R2 (SI)
Wiring Terminal
Output - L11
Input - L12
Continuous Output Current,
Max [mA]
50
ON State Voltage Drop
(P/S to +), Max [V]
0.2
Surge Output Current, Max [mA] 700
Surge Output Current Duration,
Max [ms]
5
Load Capacitance, Max [µF] 1
Off State Leakage Current, Max
[mA]
< 0.1
Short Circuit Detection No
Short Circuit Protection Yes
Galvanic Isolation:
I/O from Logic
No
Fanout (Max number of
connections to L11)
10
Cable length between L11 and
L12 [m]
30