46 Rockwell Automation Publication ENET-IN002H-EN-P - August 2017
Chapter 4 Set the Network IP Address
The 1756 EtherNet/IP communication modules are shipped with
this configuration:
BOOTP/DHCP enabled
Rotary switches set to 999 - when applicable
To reset the module factory default settings during normal module operation, see
Reset the Module IP Address to a Factory Default Value on page 54
.
These tools are used in this sequence to set the network IP address.
1. Set the Network IP Address with the Rotary Switches
2. Set the Network IP Address with the BOOTP/DHCP Server
3. Set the Network IP Address with RSLinx Software or the Studio 5000™
Environment
Set the Network IP Address with the Rotary Switches
This graphic shows the rotary switches on a 1756 EtherNet/IP communication
module. Depending on the module, the switches are on the top or the side of the
module.
At power-up, the module reads the rotary switches to determine if they are set to
a valid number for the last portion of the IP address. For example, if the numbers
are in the range from 001…254.
If the settings are a valid number, these conditions result:
IP address = 192.168.1.xxx (where xxx represents the switch settings)
Subnet mask = 255.255.255.0
Gateway address
= 192.168.1.1 for firmware revision 5.008 or later
= 0.0.0.0 for firmware revision 5.007 or earlier
32454
Rotary Switches
Front of
Module

Table of Contents

Other manuals for Rockwell Automation Allen-Bradley 1756-ENBT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley 1756-ENBT and is the answer not in the manual?

Rockwell Automation Allen-Bradley 1756-ENBT Specifications

General IconGeneral
Product TypeEthernet/IP Communication Module
SeriesControlLogix
Model Number1756-ENBT
Communication ProtocolEthernet/IP
Network Ports1
Port TypeRJ45
Data Rate10/100 Mbps
Module LocationAny slot in the ControlLogix chassis
Power SupplyBackplane
Operating Temperature0 to 60 °C
Storage Temperature-40 to 85 °C (-40 to 185 °F)
Relative Humidity5 to 95% (non-condensing)
Compatible ControllersControlLogix
CertificationsCE, UL, cUL