160 Rockwell Automation Publication 5094-UM001C-EN-P - April 2019
Appendix C Application/Wiring Examples for Safety I/O Modules
Figure 36 - 5094-IB16S Module - SIL 3, PLe, Cat. 4 in Safety Pulse Mode
Figure 37 - 5094-IB16S Module - SIL 3, PLe, Cat. 4 in Safety Mode
SIL level and Category: SIL 3, PLe, Cat. 4
Fault Exclusion: None
Point Mode: Safety Pulse Mode
SI_n(n = 0...15)
TO_n(n = 0...7)
The second SI channel can be any
channel other than SI_n+8.
Non-Equivalent Sensor
TO_n
SI_n
TO_n+1
SI_n+1
SIL level and Category: SIL 3, PLe, Cat. 4
Fault Exclusion: External Wiring fault
Point Mode: Safety Mode
SI_n(n = 0...15)
TO_n(n = 0...7)
The second SI channel can be any
channel other than SI_n+8.
Non-Equivalent Sensor
TO_n
SI_n
TO_n+1
SI_n+1