3-22 Programming and Parameters
Advanced Program Group (continued)
Stop drive before changing this parameter.
A095 [Reverse Disable]
Enables/disables the function that allows the direction of motor rotation to be changed. The reverse
command may come from a digital command, the keypad or a serial command. All reverse inputs
including two-wire Run Reverse will be ignored with reverse disabled.
Options 0 Reverse Enabled
(Default)
1 Reverse Disabled
A096 [Flying Start En]
Sets the condition that allows the drive to reconnect to a spinning motor at actual RPM.
Options 0 Disabled (Default)
1 Enabled
A097 [Compensation]
Enables/disables correction options that may improve problems with motor instability.
Options 0 Disabled
1 Electrical (Default)
2 Mechanical
3 Both
A098 [SW Current Trip]
Enables/disables a software instantaneous (within 100 ms) current trip.
Values Default 0.0 (Disabled)
Min/Max: 0.0/(Drive Rated Amps × 2)
Display: 0.1 Amps
A099 [Process Factor]
Related Parameter(s): d010
Scales the value displayed by d010 [Process Display].
Values Default 30.0
Min/Max: 0.1/999.9
Display: 0.1
Output
Freq
Process
Factor
Process
Display
=
x
userman.book Page 22 Friday, June 21, 2002 2:48 PM

Other manuals for Rockwell Automation Allen-Bradley PowerFlex 4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley PowerFlex 4 and is the answer not in the manual?

Rockwell Automation Allen-Bradley PowerFlex 4 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley PowerFlex 4
CategoryDC Drives
LanguageEnglish

Related product manuals