Programming and Parameters 3-23
Advanced Program Group (continued)
Stop drive before changing this parameter.
A100 [Fault Clear]
Resets a fault and clears the fault queue.
Options 0 Ready (Default)
1 Reset Active Fault
2 Clear Fault Queue (Parameters d007-d009 [F
ault x Code])
A101 [Program Lock]
Protects parameters against change by unauthorized personnel.
Options 0 Unlocked (Default)
1 Locked
A102 [Testpoint Sel]
Used by Rockwell Automation eld service personnel.
Values Default 400
Min/Max: 0/FFFF
Display: 1 Hex
A103 [Comm Data Rate]
Sets the serial port rate for the RS485 (DSI) port.
Important: Power to drive must be cycled before any changes will affect drive operation.
Options 0 1200
1 2400
2 4800
3 9600 (Default)
4 19.2K
5 38.4K
A104 [Comm Node Addr]
Sets the drive node address for the RS485 (DSI) port if using a network connection.
Important: Power to drive must be cycled before any changes will affect drive operation.
Values Default 100
Min/Max: 1/247
Display: 1
userman.book Page 23 Friday, June 21, 2002 2:48 PM

Other manuals for Rockwell Automation Allen-Bradley PowerFlex 4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley PowerFlex 4 and is the answer not in the manual?

Rockwell Automation Allen-Bradley PowerFlex 4 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley PowerFlex 4
CategoryDC Drives
LanguageEnglish

Related product manuals