English-26 PowerFlex 400P Adjustable Frequency AC Drive Quick Start
d325 [Fault Current] 0.0/(Drive Amps × 2) 0.1 Amps Read Only
d326 [Fault Bus Volts] 0/820 VDC 1 VDC Read Only
d327 [Status @ Fault] 0/1 1 Read Only
d328 [PID Feedbk Displ] -200.0/200.0% 0.1% Read Only
d329 [DC Bus Ripple V] 0/820 VDC 1 VDC Read Only
d330
d331
d332
d333
d334
d335
d336
[Fault 4 Code]
[Fault 5 Code]
[Fault 6 Code]
[Fault 7 Code]
[Fault 8 Code]
[Fault 9 Code]
[Fault 10 Code]
0/122 1 Read Only
d337
d339
d341
d343
d345
d347
d349
[Fault 4 Time-hr]
[Fault 5 Time-hr]
[Fault 6 Time-hr]
[Fault 7 Time-hr]
[Fault 8 Time-hr]
[Fault 9 Time-hr]
[Fault10 Time-hr]
0/32767 Hrs 1 Hr Read Only
d338
d340
d342
d344
d346
d348
d350
[Fault 4 Time-min]
[Fault 5 Time-min]
[Fault 6 Time-min]
[Fault 7 Time-min]
[Fault 8 Time-min]
[Fault 9 Time-min]
[Fault10 Time-min]
0.0/60.0 Min 0.1 Min Read Only
No. Parameter Min/Max Display/Options Default
Logic Group Parameters
No. Parameter Min/Max Display/Options Default
L351 [Counter Status] 0/9999 1 Read Only
L352 [Timer Status] 0.0/9999 Secs 0.1 Secs Read Only
L354 [Stp Logic Status] 0/7 1 Read Only
L355
L356
L357
L358
[Preset Freq 4]
[Preset Freq 5]
Preset Freq 6]
[Preset Freq 7]
0.0/320.0 Hz 0.1 Hz 30.00 Hz
40.00 Hz
50.00 Hz
60.00 Hz
L359 [Process Time Lo] 0.00/99.99 0.01 0.00
L360 [Process Time Hi] 0.00/99.99 0.01 0.00
L361 [Torque Perf Mode] 0/1 0 = “V/Hz” 1 = “Sensrls Vect” 1
L363 [Autotune] 0/2 0 = “Ready/Idle” 1 = “Static Tune”
2 = “Rotate Tune”
0
L364 [IR Voltage Drop] 0.0/230.0 VAC 0.1 VAC Drive Rating
L365 [Flux Current Ref] 0.00/[Motor NP FLA] 0.01 Amps Drive Rating
L366 [Jog Frequency] 0.00/[Maximum Freq] 0.01 Hz 10.00 Hz
L367 [Jog Accel/Decel] 0.1/600.0 Secs 0.1 Secs 10.0 Secs
L368 [DB Resistor Sel] 0/99 0 = “Disabled”
1 = “Normal RA Res”
2 = “NoProtection”
3-99 = % of Duty Cycle
0
L369 [MOP Reset Sel] 0/1 0 = “Zero MOP Ref 1 = “Save MOP Ref” 1
L370-
L377
[Stp Logic 0-7] 0001/FAFF 4 Digits 00F1
L380-
L387
[Stp Logic Time 0-7] 0.0/999.9 Secs 0.1 Secs 30.0 Secs
L388 [Outpt Volt Scale] 0/100% 1% 100%
Input State of
Digital In 1
(I/O Terminal 05)
Input State of
Digital In 2
(I/O Terminal 06)
Input State of
Digital In 2
(I/O Terminal 07)
Frequency Source Accel / Decel Parameter Used
(2)
0 0 1 [Preset Freq 4] [Accel Time 1] / [Decel Time 1]
1 0 [Preset Freq 5] [Accel Time 1] / [Decel Time 1]
0 1 1 [Preset Freq 6] [Accel Time 2] / [Decel Time 2]
1 1 1 [Preset Freq 7] [Accel Time 2] / [Decel Time 2]
(2)
When a Digital Input is set to “Accel 2 & Decel 2”, and the input is active, that input overrides the settings in this table.
22P-QS001C-EN-P.fm Page 26 Thursday, March 30, 2017 5:55 PM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley PowerFlex 400P Series and is the answer not in the manual?

Rockwell Automation Allen-Bradley PowerFlex 400P Series Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley PowerFlex 400P Series
CategoryDC Drives
LanguageEnglish

Related product manuals