3-10 Programming and Parameters
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22B-UM001I-EN-E
Basic Program Group (continued)
P036 [Start Source] Related Parameter(s): d012, P037
Stop drive before changing this parameter.
Sets the control scheme used to start the drive.
Refer to Start and Speed Reference Control
on page 1-23 for details about how other drive settings
can override the setting of this parameter.
Important: For all settings except option 3, the drive must receive a leading edge from the start input
for the drive to start after a stop input, loss of power or fault condition.
Options 0 “Keypad” (Default) Integral keypad controls drive operation.
I/O Terminal 1 “Stop” = coast to stop.
When active, the Reverse key is also active unless
disabled by A095
[Reverse Disable].
1 “3-Wire” I/O Terminal 1 “Stop” = stop according to the value set in
P037
[Stop Mode].
2 “2-Wire” I/O Terminal 1 “Stop” = coast to stop.
3 “2-W Lvl Sens” Drive will restart after a “Stop” command when:
Stop is removed
and
Start is held active
4 “2-W Hi Speed” Important: There is greater potential voltage on the output
terminals when using this option.
Outputs are kept in a ready-to-run state. The drive will
respond to a “Start” command within 10 ms.
I/O Terminal 1 “Stop” = coast to stop.
5 “Comm Port” Remote communications. Refer to Appendix C for details.
I/O Terminal 1 “Stop” = coast to stop.
6 “Momt FWD/REV” Drive will start after a momentary input from either the
Run FWD Input (I/O Terminal 02) or the Run REV Input (I/
O Terminal 03).
I/O Terminal 1 “Stop” = coast to stop.
!
ATTENTION: Hazard of injury exists due to unintended operation.
When P036 [Start Source] is set to option 3, and the Run input is
maintained, the Run inputs do not need to be toggled after a Stop input for
the drive to run again. A Stop function is provided only when the Stop input
is active (open).
22B-UM001.book Page 10 Tuesday, May 30, 2017 5:22 PM

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen Bradley PowerFlex40 and is the answer not in the manual?

Rockwell Automation Allen Bradley PowerFlex40 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen Bradley PowerFlex40
CategoryDC Drives
LanguageEnglish

Related product manuals