Page #169 background imageLoading...
Page #169 background image
Publication 2711P-UM001I-EN-P - December 2008 169
Terminal Connections Chapter 7
PanelView Plus and PanelView Plus CE Terminals to PLC-5 and MicroLogix Controllers
Cables: PanelView Plus and PanelView Plus CE to PLC-5 and MicroLogix
Controllers
Protocol PanelView Plus Comm Port
PLC-5, PLC-5C, PLC-5E
CH0 (25-pin RS-232)
(DF1)
MicroLogix 1500LRP
CH1 (9-pin RS-232)
(DF1 or DH-485)
MicroLogix 1000, 1200,
1500LSP
CH0 (8-pin Mini DIN)
(DF1 or DH-485)
DF1
(any)
RS-232 (DF1) Comm Port (9-pin)
PanelView Plus 400 to 1500
2711P-RN22C
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
2706-NC13 (3 m/10 ft)
(9-to-25 pin adapter required)
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
2706-NC13 (3 m/10 ft)
2711-NC21 (5 m/16 ft)
2711-NC22 (15 m/49 ft)
(null modem not required)
(2)
(2)
AIC+ Module recommended for isolation purposes when PanelView and controller are not on same power supply.
DH-485
(any)
RS-232 (DH-485) Comm Port (9-pin)
PanelView Plus 400 to 1500
2711P-RN22C
N/A
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
2706-NC13 (3 m/10 ft)
2711-NC21 (5 m/16 ft)
2711-NC22 (15 m/49 ft)
(null modem not required)
(2)
DH-485 Communication Port
PanelView Plus 400 to 1500
2711P-xxx3xx, -xxx6xx, 2711P-RN3
(1)
, 2711P-RN6
(1)
For CE compliance, use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft).
N/A N/A
Use AIC+ Module
(1761-NET-AIC)
Connect to Port 3
ControlNet
xxx15xx
ControlNet Communication Port
PanelView Plus 400 and 600
2711P-RN15C
PanelView Plus 400 to 1500
2711P-xxx15xx, 2711P-RN15S
To PLC-5C with
ControlNet Cable
N/A N/A
DeviceNet
DeviceNet Communication Port
PanelView Plus 400 and 600
2711P-RN10C
PanelView Plus 700 to 1500
2711P-RN10H
Use 1771-SDN Module
with DeviceNet Cable
N/A N/A
EtherNet/IP
(any except
xx5xx)
EtherNet/IP Comm Port
PanelView Plus 400 to 1500
(except 2711P-xxx5xx)
To PLC-5E with
Ethernet Cable
Use 1761-NET-ENI Module
with Ethernet Cable
Remote I/O
xxx1xx
xxx6xx
Remote I/O Communication Port
PanelView Plus 400 to 1500
2711P-xxx1xx, -xxx6xx, 2711P-RN1, 2711P-RN6
Shielded Twinaxial Cable
(1770-CD)
N/A
N/A
DH+
xxx6xx
xxx8xx
DH+ Communication Port
PanelView Plus 400 to 1500
2711P-xxx6xx, -xxx8xx, 2711P-RN6, 2711P-RN8
Shielded Twinaxial Cable
(1770-CD)
N/A
N/A

Table of Contents

Other manuals for Rockwell Automation PanelView Plus 700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PanelView Plus 700 and is the answer not in the manual?

Rockwell Automation PanelView Plus 700 Specifications

General IconGeneral
BrandRockwell Automation
ModelPanelView Plus 700
CategoryTouch terminals
LanguageEnglish

Related product manuals