168 Publication 2711P-UM001I-EN-P - December 2008
Chapter 7 Terminal Connections
Logic Controller Cable
Charts
The charts provide a summary of terminal connections to controllers
and network interface modules.
Runtime Communication Cables - To Controller
PanelView Plus and PanelView Plus CE Terminals to SLC Controllers
Cables: PanelView Plus and PanelView Plus CE to SLC Controllers
Protocol PanelView Plus Comm Port
SLC-500, 5/01, 5/02
CH1 RJ45
(DH-485)
SLC-5/03, 5/04, 5/05
CH0 (9-pin RS-232)
(DF1 or DH-485)
SLC 5/03
CH1 (RJ45)
(DH-485)
SLC 5/04
CH1 (DH+)
SLC 5/05
CH1 (ENET)
DF1
(any)
RS-232 (DF1) Comm Port (9-pin)
PanelView Plus 400 to 1500
2711P-RN22C
N/A
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
2706-NC13 (3 m/10 ft)
N/A N/A N/A
DH-485
(any)
RS-232 (DH-485) Comm Port (9-pin)
PanelView Plus 400 to 1500
2711P-RN22C
Use AIC+ Module
(1761-NET-AIC)
Connect to Port 1 or 2
2711-NC13 (5 m/16 ft)
2711-NC14 (10 m/32 ft)
2706-NC13 (3 m/10 ft)
Use AIC+ Module
(1761-NET-AIC)
Connect to Port 1 or 2
N/A N/A
DH-485 Communication Port
PanelView Plus 400 and 600
2711P-xxx3xx, 2711P-RN3
(1)
1747-C10 (2 m/6 ft)
1747-C11 (0.3 m/1 ft)
1747-C20 (6 m/20 ft)
Use AIC+ Module
(1761-NET-AIC)
Connect to Port 3
1747-C10 (2 m/6 ft)
1747-C11 (0.3 m/1 ft)
1747-C20 (6 m/20 ft)
N/A N/A
DH-485 Communication Port
PanelView Plus 700 to 1500
2711P-xxx6xx, 2711P-RN6
1761-CBL-AS03
(3 m/10 ft)
1761-CBL-AS09
(9 m/30 ft)
Use AIC+ Module
(1761-NET-AIC)
Connect to Port 3
1761-CBL-AS03
(3 m/10 ft)
1761-CBL-AS09
(9 m/30 ft)
N/A N/A
ControlNet
xxx15xx
ControlNet Communication Port
PanelView Plus 400 and 600
2711P-RN15C
PanelView Plus 700 to 1500
2711P-xxx15xx, 2711P-RN15S
N/A
1747-KFC15A or
1747-SCRNR/A Module with ControlNet Cable
DeviceNet
xxx10xx
DeviceNet Communication Port
PanelView Plus 400 and 600
2711P-RN10C
PanelView Plus 700 to 1500
2711P-RN10H
N/A
Use 1747-SDN Module
with DeviceNet Cable
EtherNet/IP
(any except
xxx5xx)
EtherNet/IP Comm Port
PanelView Plus 400 to 1500
(except 2711P-xxx5xx)
N/A
Use 1761-NET-ENI Module
with Ethernet Cable
N/A N/A
2711P-
CBL-EX04
Ethernet
Crossover
Cable
(2)
Remote I/O
xxx1xx
xxx6xx
Remote I/O Communication Port
PanelView Plus 400 to 1500
2711P-xxx1xx, -xxx6xx, 2711P-RN1, 2711P-RN6
SLC 5/02 only
Use 1747-SN with
Shielded Twinaxial Cable
(1770-CD)
Use 1747-SN Module with Shielded Twinaxial Cable (1770-CD)
DH+
xxx6xx
xxx8xx
DH+ Communication Port
PanelView Plus 400 to 1500
2711P-xxx6xx, -xxx8xx, 2711P-RN6, 2711P-RN8
N/A N/A N/A
Shielded
Twinaxial
Cable
(1770-CD)
N/A
(1)
For CE compliance, use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft).
(2)
PanelView Plus EtherNet/IP direction connection to SLC 5/05 requires hub or crossover cable listed.