Quick Installation Guide
00825-0100-4664, Rev BB
January 2013
Rosemount 8712 / 8700 Series
28
Canadian Standards Association (CSA)
N0 Non-incendive for Class I, Division 2
Groups A, B, C, and D non-flammable fluids
(T4 at 40 °C)
Dust-ignition proof Class II/III, Division 1
Groups E, F, and G
(T4 at 40 °C)
Hazardous Locations; Enclosure Type 4X
European Certifications
N1 ATEX Type n
Certificate No: Baseefa 05ATEX0170X
II 3G EEx nA nL IIC T4 (-40 °C Ta +60 °C)
Vmax = 42 V DC
IP 66
0575
Special Conditions for Safe Use (x)
The apparatus is not capable of withstanding the 500V electrical strength test required
by Clause 8.1of EN 60079-15: 2003. This must be taken into account when installing
the apparatus.
International Certifications
IECEx
N7 IECEx Type n
Certificate No: IECEx BAS 07.0036X
Ex nA nL IIC T4 (Ta = -40 °C to + 60 °C)
V
max
= 42 V DC
Special Conditions for Safe Use (x)
The apparatus is not capable of withstanding the 500V electrical strength required by
Clause 6.8.1of IEC 60079-15: 2005. This must be taken into account when installing
the apparatus.
InMetro - Brazil
N2 Non-incendive, Type n
Certificate No: NCC 11.0198X
Ex nA ic IIC T4 Gc (-40 °C Ta +60 °C)
V
max
= 42 V DC
4664RevBBQIG.fm Page 28 Friday, January 11, 2013 6:13 PM