RS900 Family Installation Guide
2.2.2 DC Power Supply Wiring and Grounding
Figure 5 - DC Power supply wiring and grounding diagram
The low voltage DC power supply features reverse polarity protection and dual
independent inputs. The latter feature allows the connection of two DC sources with the
same nominal voltage to provide redundant power supply inputs.
The DC power supply inputs should be connected as follows:
1. Connect to the DC inputs according to the polarity markings on the unit.
2. Surge Ground should be connected to the Chassis Ground via a braided cable or
other appropriate grounding wire. Surge Ground is used as the ground conductor
for all surge and transient suppression circuitry internal to the unit.
3. Chassis Ground must be connected to the protective earth.
NOTES:
1. Equipment must be installed according to the applicable country wiring codes.
2. All line-to-ground transient energy is shunted to the Surge Ground terminal. In
cases where users require the inputs to be isolated from ground, remove the
ground braid between Surge and Chassis Ground. Note that all line-to-ground
transient protection circuitry will be disabled.