RS900 Family Installation Guide
7.2 IEEE 1613 Type Tests
IEEE
Test
IEEE
1613
Clause
Description Test Levels
Enclosure Contact +/- 8kV
C37.90.
3
9 ESD
Enclosure Air +/- 15kV
C37.90.
2
8 Radiated RFI Enclosure ports 35 V/m
Signal ports +/- 4kV @ 2.5kHz
D.C. Power ports +/- 4kV
A.C. Power ports +/- 4kV
C37.90.
1
7 Fast Transient
Earth ground ports +/- 4kV
Signal ports 2.5kV common mode @ 1MHz
D.C. Power ports
2.5kV common & differential mode @
1MHz
C37.90.
1
7 Oscillatory
A.C. Power ports
2.5kV common & differential mode @
1MHz
Signal ports 5 kV (Failsafe Relay)
D.C. Power ports 5 kV
C37.90 6 H.V. Impulse
A.C. Power ports 5 kV
Signal ports 2kV AC(Failsafe Relay)
D.C. Power ports 1.5kV DC
C37.90 6
Dielectric
Strength
A.C. Power ports 2kV AC
Table 26 - IEEE 1613 Type Tests
NOTE:
If the unit contains copper ports the IEEE 1613 conformance is Class 1 (During
disturbance errors may occur but recovery is automatic).
If the unit contains all fiber ports the IEEE 1613 conformance is Class 2 (During
disturbance no errors will occur).
7.3 IEC Environmental Type Tests
Test Description Test Levels
Severity
Levels
IEC 60068-2-1 Cold Temperature Test Ad -40 deg. C, 16 Hours N/A
IEC 60068-2-2 Dry Heat Test Bd +85 deg. C, 16 Hours N/A
IEC 60068-2-
30
Humidity (Damp
Heat, Cyclic)
Test Db
95% (non-condensing), 55°C, 6
cycles
N/A
IEC 60255-21-
1
Vibration 2g @ (10-150) Hz Class 2
IEC 60255-21-
2
Shock 30g @ 11 ms Class 2
Table 27 - Environmental Type Tests
2010 RuggedCom Inc. 43 Rev107