RS900 Family Installation Guide
2.2.4 Dielectric Strength Testing
Units which are to have dielectric strength testing (HIPOT testing) done in the field must
have the braided ground cable disconnected during the test. This is required in order to
prevent the surge suppression circuitry, which is connected to surge ground, from being
activated.
Figure 7 - Dielectric Strength Testing
2010 RuggedCom Inc. 20 Rev107