PDM20 Series
-56-
3. Two wire sensor wiring diagram
M1 M2 GND +VO AI
Warm tip: For a 9-36V power supply pressure transmitter,
it is recommended to use 24V power supply
2.Set pressure parameters:
P0.38=1
P0.03=16
P0.04=1
P0.05=24
3.Set target pressure:
P0.00=3.0
P0.01=0.3
4.Choose auto-start mode:
P0.14=11
5.Check rotation direction
of pump:
Shortly start pump, check
the direction of pump, if the
pump direction error,
change the pdrameter P0.02.
6.Observe the effect of
constant pressure:
Observe the effect of
constant pressure, if the
pressure is constant, that is
OK; if the pressure
fluctuations large , please
reference common fault
handling tutorial.
8.Warm tips
a: Water supply system
must be equipped with a
check valve, five way
valve is a kind of check
valve.
b: For a new pump,when it
runs without pressure,
emptying is suggested.
PDM20-Two wire 9-36V sensor wiring diagram
Pressure
transmitter
Type
PT1100
Power
9-36VDC
Range
0-1.6Mpa
Output
4-20mA
Power line
red
Singal line
green
Red line connected to +VO
Green line connected to AI
Before connecting, check the
voltage between +VO and GND
using a multimeter
1.Installation and wiring:
Connect the power cable
and the sensor cable
according to the diagram.
7.Sleep test:
Close the water outlet, the
drive output frequency will
be reduced until shutdown;
if it can not sleep, please
refer to the common fault
handling tutorial.