Loading...
PDS33 Series
- 33 -
Function
Code
Function
Description
Unit
Factory
setting
Modification
Type
Communicati
on Address
protection gain
FA.02
Early warning
coefficient of
motor overload
protection
50% ~ 100%
1%
80%
○
FA02
FA.03
Gain of over
voltage stall
protection
0 ~ 100
1
10
○
FA03
FA.04
Value of over
voltage stall
protection
120% ~ 150%
1%
130%
○
FA04
FA.05
Gain of over
current stall
protection
0 ~ 100
1
20
○
FA05
FA.06
Value of over
current stall
protection
100% ~ 200%
1%
150%
○
FA06
FA.07
Short to
ground
protection
0:Invalid
1:valid
1
1
○
FA07
FA.08
Auto reset
times
0 ~ 5
1
0
○
FA08
FA.11
Input phase
loss protection
0:Disabled
1:Enabled
1
1
○
FA0B
FA.12
Output phase
loss protection
0:Disabled
1:Enabled
1
1
○
FA0C
FC Group:Communication parameters
FC.00
Local address
1 ~ 247,0 for
broadcast address
1
1
○
FC00
FC.01
Baud rate
0:300 bps
1:600 bps
2:1200 bps
3:2400 bps
4:4800 bps
5:9600 bps
6:19200 bps
7:38400 bps
8:57600 bps
9:115200 bps
1
5
○