PDS33 Series
- 33 -
Function
Code
Function
Description
Unit
Factory
setting
Modification
Type
Communicati
on Address
protection gain
FA.02
Early warning
coefficient of
motor overload
protection
50% 100%
1%
80%
FA02
FA.03
Gain of over
voltage stall
protection
0 100
1
10
FA03
FA.04
Value of over
voltage stall
protection
120% 150%
1%
130%
FA04
FA.05
Gain of over
current stall
protection
0 100
1
20
FA05
FA.06
Value of over
current stall
protection
100% 200%
1%
150%
FA06
FA.07
Short to
ground
protection
0Invalid
1valid
1
1
FA07
FA.08
Auto reset
times
0 5
1
0
FA08
FA.11
Input phase
loss protection
0Disabled
1Enabled
1
1
FA0B
FA.12
Output phase
loss protection
0Disabled
1Enabled
1
1
FA0C
FC GroupCommunication parameters
FC.00
Local address
1 2470 for
broadcast address
1
1
FC00
FC.01
Baud rate
0300 bps
1600 bps
21200 bps
32400 bps
44800 bps
59600 bps
619200 bps
738400 bps
857600 bps
9115200 bps
1
5
FC01