6.1 Brief introduction of function code
PD Communication Parameters
Function
Code
Parameter
Name
Setting Range Default Property
PD-01
MODBUS data
format
0: No check, data format <8,N,2>
1: Even parity check, data format
<8,E,1>
2: Odd Parity check, data format
<8,O,1>
3: No check, data format <8,N,1>
Valid for Modbus
0
PD-02 Local address
0: Broadcast address
1 ~ 247
1
PD-03
MODBUS
response delay
0 ~ 20ms 2
PD-04
Communication
timeout
0.0: invalid
0.1 ~ 60.0s
0.0
PD-05
Modbus protocol
selection and
PROFIBUS-DP
data format
Unit's digit: Modbus protocol
0: Non-standard Modbus protocol
1: Standard Modbus protocol
Ten's digit: PROFIBUS-DP data
format
0: PPO1 format
1: PPO2 format
2: PPO3 format
3: PPO5 format
30
PD-06
Communication
reading current
resolution
0: 0.01A
1: 0.1A
0