8 | EN MCB_miniMCB v2019.1
5.13. DISPLAY AND CANCELLATION OF ALARMS AND WARNINGS
The system noties the user about the system failures by warnings that are canceled automatically and by alarms that have to be canceled man-
ually. The latter are recommended to be canceled by a specialist prior to nding out the causes of the alarm. Information on alarms and warnings
is also displayed in the main window ADJUSTER › VENTILATION CONTROL. If at least one alarm is active, the system is shut down and external failure
indication is activated. Alarms and warnings can be reviewed and canceled in the window ADJUSTER › ALARMS or USER › ALERT. All possible alarms
and warnings are provided in the table below.
INDICATION ALARMS LIST INDICATION ALARMS LIST
.
Warning! Rotor broken belt alarm
A.3
Alarm! Controller cabinet temperature sensor fail-
ure. System stopped
A.2
Alarm! Fireplace protection activated
.32
Fire damper test OK
.3
Warning! Dryness protection activated
.33
Warning! Fire damper test failed
.
Warning! Plate heat exchanger frost protection
activated
A.3
Alarm! Heater manual protection. System stopped!
A.5
Alarm! Plate heat exchanger frost protection system
stopped
.35
Warning! Heater automatic protection
.6
Warning! Plate heat exchanger frost protection (pres-
sure relay)
A.36
Alarm! Pre-heater manual protection. System
stopped!
A.7
Alarm! Hydronic heater frost protection. System
stopped
.37
Warning! Pre-heater automatic protection
.
Warning! Too low supply temperature
A.3
Alarm! Supply fan failure
.
Warning! Too high supply temperature
A.3
Alarm! Extract fan failure
A.
Alarm! Too low supply temperature. System stopped
.
Warning! DX cooler failure
A.
Alarm! Too high supply temperature. System stopped
A.
Alarm! Fire
.2
Warning! Change supply air lter (pressure relay)
A.2
Alarm! Supply fan pressure protection. System
stopped
.3
Warning! Change extract air lter (pressure relay)
A.3
Alarm! Extract fan pressure protection. System
stopped.
.
Warning! Change supply and extract lters (timeout)
A.
Alarm! Internal system error.
A.5
Alarm! Power supply failure. Please, check F1 fuse
A.5
Alarm! Heater manual protection. Boosting.
.6
Warning! Supply air temperature sensor failure.
Emergency run
A.6
Alarm! Pre-heater manual protection. Boosting.
.7
Warning! Extract air temperature sensor failure.
Emergency run
A.7
Alarm! Internal communication error
.
Warning! Exhaust air temperature sensor failure.
Emergency run
.
Warning! DX cooler defrosting
.
Warning! Outdoor air temperature sensor failure.
Emergency run
.
Warning! Too high 3 days extract humidity. Increas-
ing air ow.
.2
Warning! Hydronic heater water temperature sensor
failure. Emergency run
.5
Warning! Too high extract humidity. Boosting.
.2
Warning! Hydronic pre-heater water temperature sen-
sor failure. Emergency run
A.5
Alarm! Rotor broken belt alarm. System stopped.
.22
Warning! Hydronic cooler water temperature sensor
failure. Emergency run
.52
Warning! Gas heater failure
.23
Warning! Controller cabinet temperature sensor
failure. Emergency run
.53
Warning! Gas pre-heater failure
A.2
Alarm! Supply air temperature sensor failure. System
stopped
.5
Warning! Too high condensation level
A.25
Alarm! Extract air temperature sensor failure. System
stopped
.55
Warning! Supply fan failure. Emergency run
A.26
Alarm! Exhaust air temperature sensor failure. Sys-
tem stopped
.56
Warning! Extract fan failure. Emergency run
A.27
Alarm! Outdoor air temperature sensor failure. Sys-
tem stopped
.57
Warning! Too low supply air ow for DX cooler
A.2
Alarm! Hydronic heater water temperature sensor
failure. System stopped
A.5 Alarm! Bypass damper failure. System stopped.
A.2
Alarm! Hydronic pre-heater water temperature sensor
failure. System stopped
A.5
Alarm! Hydronic heater/pre-heater circ. pump
failute. System stopped.
A.3
Alarm! Hydronic cooler water temperature sensor
failure. System stopped
W.6
Warning! Hydronic heater/pre-heater circ. pump
failute.
5.14. EVENT LOG (HISTORY)
The system records 50 recent events (failures, alarms, re damper testing results, etc.).
The log stores the description of events and time.
The event log may be reviewed in the window ADJUSTER › HISTORY or USER › MENU › HISTORY.