EB 5573 EN 16-37
Appendix A (conguration instructions)
16.2.1.2 Gradient characteristic
Basically,thefollowingruleapplies:adecreaseintheoutdoortemperaturecausestheow
temperature to increase in order to keep the room temperature constant. By varying the 'Gra-
dient' and 'Level' parameters, you can adapt the characteristic to your individual require-
ments:
t
A
+20 0 –20
VL
The gradient needs to be increased if the room temperature
drops when it is cold outside.
t
A
°C
+20 0 –20
VL
The gradient needs to be decreased if the room temperature
drops when it is cold outside.
VL
t
A
+20 0 –20
The level needs to be increased and the gradient decreased
if the room temperature drops when it is mild outside.
VL
t
A
+20 0 –20
The level needs to be decreased and the gradient increased
if the room temperature rises when it is mild outside.