16-42 EB 5573 EN
Appendix A (conguration instructions)
Whentheadditionalreadingintheowtemperaturereadingdisappearsafterthelast
phase, this indicates that the drying process has been completed. Any power failure that oc-
curs while the function is running automatically restarts the drying function.
In systems in which the drying function had to be interrupted due to DHW heating (e.g. sys-
temAnl2.1,seepage16-12),storagetankchargingdoesnotoccurwhilethedryingfunc-
tion is active, provided it is not used for frost protection of the storage tank.
The function block parameters can only be accessed after after starting the function by deac-
tivating and activating the function block again.
Functions Default Conguration
Underoorheating/dryingofjointless
oors
0
0.0°C
25.0°C
0
5.0°C
45.0°C
4
0.0°C
SToP
CO1,2->F05-1
Boost:0.0to50.0°C
Starttemperature:20.0to60.0°C
Hold (days): 0 to 10 days
Temp.rise/day:0.0to10.0°C
Maximumtemperature:25.0to60.0°C
Hold (days): 0 to 10 days
Temp.reduction/day:0.0to10.0°C
STArT,
STArT,
STArT,
STArT
16.2.4 Night set-back
Thenightset-back(=differenceoftheowtargettemperatureinratedandreducedmode)is
calculated in all heating circuits with a gradient characteristic as follows:
2x Heating characteristic gradient x (day room temperature – night room temperature)
16.2.4.1 OT activation value in rated operation
If a heating circuit is in reduced operation (automatic mode), this circuit is switched to rated
operation whenever the outdoor temperature falls below 'OT activation value in rated opera-
tion'. Reduced operation restarts after the outdoor temperature rises above the limit (plus
0.5°Chysteresis).
This function prevents the building from cooling down excessively outside the times-of-use
whenlowoutdoortemperaturesoccur.Thetransitiontowardsratedmodecanbecongured
to be variable depending on the outdoor temperature.
Note