EasyManua.ls Logo

Samson TROVIS 5573 - Page 159

Samson TROVIS 5573
200 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EB 5573 EN 16-77
Appendix A (conguration instructions)
16.5 Communication
Using the optional RS-485 communication
module (Modbus RTU interface for two-
wirebusnetworks),theTROVIS5573
Heating Controller can communicate with
a control system. In combination with a
suitable software for process visualization
and communication, a complete control
system can be implemented.
The operating software can be updated
over a data cable, provided Modbus has
been activated (CO6->F01-1).
RS-232
RS-485
RS-232C
TROVIS 5573
RS-485
1
1
GLT
1: Optional RS-485 communication module
Fig.16-9: Network structure
16.5.1 RS-485 communication module
When looking onto the controller front, the connection for the optional communication mod-
ule (icon, order no. 8812-2002) is located on the left side of the controller housing (RJ-45
connectorsocket).Thebuslinelinksthecontrolunits/devicesinanopenring.Attheendof
the bus line, the data cable is connected to the control station using an RS-485 to RS-232
converter (e.g. CoRe02).
The maximum range of the bus connection (cable length) is 1200 meters. For greater distanc-
es, repeaters (e.g. CoRe02) must be used to regenerate the signal level. A maximum of 246
devices with 8-bit addressing can be connected to a bus.
If no communication is established between the control system and controller, the time of ac-
cess by the control system can be restricted to dynamic process by the monitoring function.
The controller resets the monitoring function, provided the valid Modbus requests are regis-
tered. However, in case of an error, all level bits are initialized back to “autonomous” after
30 minutes have elapsed.
Note

Related product manuals