EB 5573 EN 16-83
Appendix A (conguration instructions)
CO1': Rk1 · Heating circuit 1 (not system Anl1.9)
1)
F Function WE Anl
Comments
Function block parameters: value range (default setting)
00 Demand only 0
All
1)
CO1'->F00-1:Rk1worksasafeedercircuit.Rk1onlypro-
cessesexternaldemandforheating;UP1runsdependingon
demand.
03 Discharging
protection
0
16.x
CO1'->F03-1:dischargingprotectionactive
04 Variable night
set-back
0
1.5, 1.6,
3.x, 16.x
CO1'->F04-1:variablenightset-back
(onlywhenCO1->F11-0)
Function block parameters:
OTLnight100%:–50to+20.0°C(+5.0°C)
OTLday0%:–50to+5.0°C(–15.0°C)
F Function block number, WE Default setting, Anl System code number
CO2: Rk2 · Heating circuit 2 (systems Anl 3.x, 4.x, 10.0, 16.6)
1)
F Function WE Anl
Comments
Function block parameters: value range (default setting)
01 Room sensor
RF2
0
All
1)
CO2->F01-1:TemperaturereadingandFG2inputfor
Type5244and5257-5orType5257-51RoomPanelsactive
02 Outdoor sensor 1
All
1)
CO2->F02-1:withoutdoorsensorAF1,outdoor-tempera-
ture-compensated control active
03 Returnow
sensor RüF2
1
10.x
CO2->F03-1:
Sensor and limitation function active
Function block parameters:
KP (limiting factor): 0.1 to 10.0 (1.0)
0
3.0, 4.x,
16.6
04 Cooling control 0
All
1)
CO2->F04-1:Coolingcontrol,onlywhenCO2->F11-1
The cooling control function causes a reversal of the operating
directionandaminimumlimitationofthereturnowtempera-
ture in RK2.
05 Underoor
heating
Drying of joint-
lessoors
0
All
1)
CO2->F05-1:Restrictionoftheadjustmentranges
Function block parameters:
Boost:0.0to50.0°C(0.0°C)
Starttemperature:20.0to60.0°C(25°C)
Hold (days): 0 to 10 days (0)
Temp.rise/day:0.0to10.0°C(5.0°C)
Maximumtemperature:25.0to60.0°C(45.0°C)
Hold (days): 0 to 10 days (4)
Temp.reduction/day:0.0to10.0°C(0.0°C)
SToP,
STArT,
STArT,
STArT,
STArT