16-104 EB 5573 EN
Appendix A (conguration instructions)
Heating circuit 1 and Rk2 (heating circuit 2)
Levels 1 and 2 parameters PA1 PA2 Value range
Flow gradient 0.2 to 3.2
Flow level –30.0to+30.0°C
Min.owtemperature –5.0to+150.0°C
Max.owtemperature 5.0to150.0°C
Four-point characteristic
Outdoor temperature, point 1 –50.0to+50.0°C
Outdoor temperature, point 2 –50.0to+50.0°C
Outdoor temperature, point 3 –50.0to+50.0°C
Outdoor temperature, point 4 –50.0to+50.0°C
Flow temperature, point 1 –5.0to+150.0°C
Flow temperature, point 2 –5.0to+150.0°C
Flow temperature, point 3 –5.0to+150.0°C
Flow temperature, point 4 –5.0to+150.0°C
Reducedowtemperature,point1 –5.0to+150.0°C
Reducedowtemperature,point2 –5.0to+150.0°C
Reducedowtemperature,point3 –5.0to+150.0°C
Reducedowtemperature,point4 –5.0to+150.0°C
Returnowtemperature,point1 5.0to90.0°C
Returnowtemperature,point2 5.0to90.0°C
Returnowtemperature,point3 5.0to90.0°C
Returnowtemperature,point4 5.0to90.0°C
OT deactivation value in rated operation 0.0to50.0°C
OT deactivation value in reduced operation –50.0to+50.0°C
OT activation value in rated operation –50.0to+5.0°C
Returnowgradient 0.2 to 3.2
Returnowlevel –30to+30.0°C
Basepointforreturnowtemperature: 5.0to90.0°C
Flow set point, day –5.0to+150°C
Flow set point, night –5.0to+150°C
Minimum set point to charge buffer tank OTto90.0°C
Stop charging of the buffer tank OTto90.0°C
Charging temperature boost 0.0to50.0°C
Lag time for storage tank charging pump 0.0 to 10.0
Set point boost (primary exchanger control) 0.0to50.0°C
Set point for binary demand processing 0.0to150°C