EB 5573 EN 16-105
Appendix A (conguration instructions)
F Function block parameters CO1 CO1' CO2 CO2' Value range
03-1 KP (limiting factor) – 0.1 to 10.0
04-1 Variable night set-back, OTL night – – –50to+20°C
04-1 Variable night set-back, OTL day – – –50to+5°C
05-1 Boost – – 0.0to50.0°C
05-1 Start temperature – – 20.0to60.0°C
05-1 Hold (days) – – 0 to 10 days
05-1 Temp.rise/day – – 0.0to10.0°C
05-1 Maximum temperature – – 25.0to60.0°C
05-1 Hold (days) – – 0 to 10 days
05-1 Temp.reduction/day – – 0.0to10.0°C
09-1 Cycle time – – 0/1to100min
09-1 KP (gain) – – 0.0 to 25.0
12-1 KP (gain) – – 0.1 to 50.0
12-1 Tn (reset time) – – 1 to 999 s
12-1 TV (derivative-action time) – – 0 to 999 s
12-1 TY (valve transit time) – – 15 to 240 s
12-0 Hysteresis – – 1.0to30.0°C
12-0 Min. ON time – – 0to10min
12-0 Min. OFF time – – 0to10min
13-1 Max. system deviation – – 3.0to10.0°C
14-1 Binary input – – BI=1,BI=0
17-1 Binary input – – – BI=1,BI=0
18-1 Lower transmission range – – – 0.0to150.0°C
18-1 Upper transmission range – – – 0.0to150.0°C
18-1 Boost flow temperature demand – – – 0.0to30.0°C
21-1 Start speed reduction – – – 5to90°C
21-1 Stop speed reduction – – – 5to90°C
21-1 Min. speed signal – – – 0to10V
23-1 Set point of differential temperature
control
– – – 0.0to50.0°C
23-1 KP(inuencefactor) – – – 0.1 to 10
23-1 Minimum speed – – – 0to100%