EB 5573 EN 5-5
Installation
Risk of fatal injury as a result of failing to
observe the permissible touch voltage.
Separation of the circuits is absolutely
essential when SELV equipment is connected
to terminals 20, 22, 25 and 28 as this
equipment has a different intended use of
the supply voltage than specied in the
technical data (230VAC).
The creepage and clearance present in the
base and controller do not guarantee the
required dielectric strength and the safe
separation of the 230V supply voltage and
the other circuits.
Î Take appropriate safety precautions (e.g.
by using coupling relays for the control
of electric actuators operated with 24V
or for ELV fault signaling contacts).
Î Only connect 230V equipment.
DANGER
!