EB 5573 EN 7-5
Start-up and conguration
7.3 Changing parameters
Depending on the system code number selected and the activated functions, not all parame-
terslistedintheparameterlistintheappendix(seeAppendixA)mightbeaccessible.
The parameters are grouped by topics:
− PA1: RK1 (heating circuit 1)
− PA2: RK2 (heating circuit 2)
− PA4: DHW circuit
− PA5: System-wide
− PA6: Communication parameters
1. Turn the rotary switch to
(parameterandcongurationlevel).
Reading: 0 0 0 0
2. Enter valid key number [q].
3. Conrmkeynumber[Û].
Reading: PA_
4. Select parameter level [q].
5. Open parameter level [Û].
6. Select parameter [q].
7. Activate editing mode for the parameter [Û].
blinks.
8. Change parameter [q].
9. Conrmparameter[Û].
Î To set further parameters in the opened parameter level, repeat the steps 6 to 9.
10. Select End [q].
11. Exit parameter level [Û].
Î To set further parameters in another parameter level, repeat the steps 4 to 9.
12. Turn the rotary switch back to normal switch setting
(information level).
All parameter settings are saved in a non-volatile memory in the controller.