8.3 Entering day and night set points
For the heating circuits, the desired room temperatures during the day ('Day set point') and
during the night ('Night set point') can be entered into the controller. In the DHW circuit, the
temperature you wish the DHW to be heated to can be set.
Switch position
Parameters Default Value range
Day set point RK1, RK2 20°C –5.0to+150.0°C
DHW temperature set point 60°C Min. to max. DHW temperature
Switch position
Parameters Default Value range
Night set point RK1, RK2 15°C –5.0to+150.0°C
DHW temperature set point 40°C Min. to max. DHW temperature
How to proceed:
1. Turn the rotary switch to the required data point.
for the day set point and DHW temperature set point
for the night set point and DHW temperature sustaining value
blinks.
InsystemsAnl1.0,1.9and3.5,thecurrentsetpointisdirectlydisplayed.Thefollowing
steps 2 and 3 (to select the control circuit) are not required.
2. Select the control circuit for which the set point is to be set [q]:
1: Heating circuit 1
2: Heating circuit 2
3: DHW circuit
Only those control circuits are available for selection which can be controlled by the se-
lected system.
3. Conrmtheselectedcontrolcircuit[Û].
Reading: Current set point
4. Adjust the set point [q].
5. Turn the rotary switch back to normal switch setting
(information level).