10.1 Recommended inspection and testing
We recommend inspection and testing according to Table 10-1.
Table 10-1: Recommended inspection and testing
Inspection and testing Action to be taken in the event of a negative
result
Check the markings, labels and nameplates on
the controller for their readability and complete-
ness.
Î Immediately renew damaged, missing or
incorrect nameplates or labels.
Î Clean any inscriptions that are covered with
dirt and are illegible.
Check the electric wiring. Î If any wires are loose, open the controller
housing and tighten the terminal screws (see
the 'Installation' chapter).
Î Renew damaged wires.
Checkwhetherthermwareisuptodate. Î Download the currently valid software at
uwww.samsongroup.com > DOWNLOADS
> Software & Drivers > Firmware
1)
.
Compare the temperature values displayed at the
controller with the actual temperatures at the point
of measurement.
Î If the displayed and actual temperatures
differ, calibrate the sensors (see the' Start-up
andconguration'chapter).
1)
SeeChapter10.2.
The SAMSON NE53 newsletter keeps users up to date on any software or hardware revi-
sions in accordance with NAMUR Recommendation NE53. You can subscribe to the news-
letter at www.samsongroup.com > SERVICE > NE53 newsletter.
Tip